TES-6830+6801 Power and Harmonics Analyzer (100A)
|
|
TES-6830+6802 Power and Harmonics Analyzer (1000A)
|
|
TES-6830+3007 Power and Harmonics Analyzer ( 3000A)
|
|
 |
|
- Analysis for 3P4W, 3P3W, 1P2W, 1P3W
- True RMS Value(V 123 and L 123 )
- Active Power(W, KW, MW, GW)
- Apparent and Reactive Power (KVA, KVAR)
- Power Factor (PF), Phase Angle (Φ)
- Energy (WH, KWH, KVARH, PFH)
- Current Measurement from 0.1mA to 3000A, Capable of Analyzing IT Standby Power Consumption to the Maximum Demand of a Factory
- Display of 35 Parameters in One Screen(3P4W)
- rogrammable CT (1 to 600) and PT (1 to 3000) Ratios
- Display of Overlapped Voltage and Current Waveform
- 2.4M Memory with Programmable Interval (1 to 6000 seconds, 17000 Records for 3P4W System)
- Output of Waveform, Power Parameters and Harmonics at Command
- Large Dot Matrix LCD Display with Backlight
- Average Demand (AD in W, KW, MW)
- aximum Demand (MD in W, KW, MW) with Programmable Period
- Harmonic Analysis to the 99th Order
- Display of 50 Harmonics in One Screen with Waveform
- Display of Waveform with Peak Values (1024 Samples/Period)
- Analysis of Total Harmonic Distortion (%THD-F)
- Graphic Phasor Diagram with 3 Phase System Parameters
- Capture 28 Transient Events (Time+Cycles) with Programmable Threshold(%)
- 3 Phase Voltage Unbalance Ratio (VUR)
- 3 Phase Voltage Unbalance Factor (d0%, d2%)
- Calculated Unbalance Current through Neutral Line (In)
- Optical isolated USB Interface
- Built-in Timer and Calendar for Data Logging
- onductor Size: -Model 6801 30mm(approx) -Model 6802 5
- 55mm(approx),64*24mm(bus bar) -Model 3007 170mm(approx)
|
 |
|
| * Please refer to users manual for more detailed and up-to-date description of specification |
|
| AC Watt (50 or 60 Hz, PF 0.5 to 1, CT=1) |
|
Range
|
Resolution
|
Accuracy of Readings
|
|
6800+6801
|
6800+6802
|
6800+3007
|
|
5.0 – 999.9W
|
0.1W
|
±1% ± 8dgts
|
±1% ± 8dgts
|
±1% of VA Range ±8dgts
|
|
1.000 – 9.999 KW
|
0.001 KW
|
±1% ± 8 dgts
|
±1% ± 8 dgts
|
±1% of VA Range ±8dgts
|
|
10.00 – 99.99 KW
|
0.01 KW
|
±1% ± 8 dgts
|
±1% ± 8 dgts
|
±1% of VA Range ±8dgts
|
|
100.0 – 999.9 KW
|
0.1 KW
|
±1% ± 8dgts
|
±1% ± 8dgts
|
±1% of VA Range ±8dgts
|
|
1000 – 9999 KW
|
1 KW
|
±1% ± 8dgts
|
±1% ± 8dgts
|
±1% of VA Range ±8dgts
|
|
0.000 – 9.999MW
|
0.001MW
|
–
|
±1% ± 8 dgts
|
±1% of VA Range ±8dgts
|
|
| AC Current( 50 or 60Hz, Auto Range,True RMS,Crest Factor<4,CT=1) |
|
|
Range
|
Resolution
|
Accuracy of Readings
|
|
6800+6801
(Overload Protection AC200A)
|
0.050 – 9.999A
|
0.001A
|
±0.5% ± 5dgts
|
|
10.00 – 60.00A
|
0.01A
|
±0.5% ± 5dgts
|
|
60.00 – 99.99A
|
0.01A
|
±1.0% ± 5dgts
|
|
6800+6802
(Overload Protection AC2000A)
|
0.04 – 10.00A
|
0.01A
|
–
|
|
0.4A – 100.0A
|
0.1A
|
±0.5% ± 5dgts
|
|
4.0 – 1000.0A
|
1A
|
±0.5% ± 5dgts
|
|
6800+ 3007
(Overload Protection AC3500A)
|
4 – 300A
|
0.1A
|
±1% of Range ±5dgts
|
|
300.0 – 999.9A
|
0.1A
|
±1% of Range ±5dgts
|
|
1000 – 3000A
|
1A
|
±1% of Range ±5dgts
|
|
| AC Voltage (50 or 60 Hz, Auto Range, True RMS, Crest FActor<4) |
|
Range
|
Resolution
|
Accuracy of Readings
|
Range
|
Resolution
|
Accuracy of Readings
|
|
4.0V – 500.0 (Phase to Neutral)
|
0.1V
|
± 0.5% ± 5dgts
|
4.0V –600.0V (Phase to phase)
|
0.1V
|
± 0.5% ± 5dgts
|
|
| Harmonics of AC Voltage in % and in Magnitude (1 to 99th order, minimum voltage at the 50 or 60 Hz>AC 80V) |
|
Range
|
In Percentage
|
In Magnitude
|
|
Resolution
|
Accuracy of readings
|
Resolution
|
Accuracy of readings
|
|
1 – 20 th
|
0.1%
|
±2%
|
0.1 V
|
±2% ±0.5V
|
|
21 – 49 th
|
4% of reading ±2.0%
|
4% of reading ±0.5A
|
|
50 – 99 th
|
6% of reading ±2.0%
|
6% of reading ±0.5A
|
|
|
Harmonics of AC Current in % and in Magnitude
Model 6800+6801(100A)(1 to 99th order, minimum current at 50 or 60 Hz is greater than 10% of the range)
|
|
Range
|
In Percentage
|
In magnitude
|
|
Resolution
|
Accuracy of reading
|
Resolution
|
Accuracy of reading
|
|
1 – 10 th
|
0.1%
|
±0.2 of reading ±1%
|
0.1mA / 0.1A
|
±0.2% of reading ±7dgts
|
|
11 – 20 th
|
±2% of reading ±1%
|
±2% of reading ±7dgts
|
|
2 1 – 50 th (A range)
|
±5% of reading ±1%
|
±5% of reading ±7dgts
|
|
2 1 – 50 th (mA range)
|
±10% of reading ±1%
|
±10% of reading ±7dgts
|
|
5 1 – 99 th
|
±35% of reading ±1%
|
±35% of reading ±7dgts
|
|
| Model 6800+6802(1000A);6800+3007(3000A)(1 to 99th order, minimum current at the 50 or 60 Hz>20A) |
|
Range
|
In Percentage
|
In Magnitude
|
|
Resolution
|
Accuracy of reading
|
Resolution
|
Accuracy of reading
|
|
1 – 20 th
|
0.1%
|
±2%
|
0.1A(6802) / 0.3A(3007)
|
±2% of reading ±0.4A/0.6A
|
|
21 – 49 th
|
4% of reading ±2.0%
|
±4% of reading ± 0.4A/0.6A
|
|
50 – 99 th
|
6% of reading ±2.0%
|
±6% of reading ± 0.4A/0.6A
|
|
| Total Harmonic Distortion |
|
Range
|
Resolution
|
Accuracy(6801)
|
Accuracy(6802)
|
Accuracy(3007)
|
|
0.0 – 20%
|
0.1%
|
±1%
|
±2%
|
±2%
|
|
20 – 100%
|
0.1%
|
±3% of reading ±5%
|
±6% of reading ±1%
|
±6% of Range ±1%
|
|
100 – 999.9%
|
0.1%
|
±10% of reading ±10%
|
±10% of reading ±1%
|
±10% of Range ±1%
|
|
| Peak Value of Ac Voltage or AC Current ,VT=1 |
|
Range
|
Samping Time
|
Accuracy of reading
|
|
50Hz
|
39 μS
|
±5% ±30digits
|
|
60Hz
|
33 μS
|
±5% ±30 digits
|
|
| Crest Factor (C.F.) of ACV or ACA ,VT=1 |
|
Range
|
Resolution
|
Accuracy of reading
|
|
1.00 – 99.99
|
0.01
|
±5% ±30digits
|
|
|
Range
|
Resolution
|
Accuracy of reading
|
|
45 – 65Hz
|
0.1Hz
|
0.1Hz
|
|
|
Range
|
Resolution
|
Accuracy of reading
|
|
0.00 – 1.00
|
0.01
|
± 0.04
|
|
|
Range
|
Resolution
|
Accuracy of reading
|
|
-180 。 to 180 。
|
0.1 。
|
± 1 。
|
|
| Conductor Size (6801) |
約30mm (approx) |
| Conductor Size (6802) |
約55mm(approx.), 64 X 24mm(Bus Bar) |
| Battery Type |
1.5V SUM-3 x 8 |
| Display |
Dot Matrix LCD with backlight |
| Power Consumption |
140mA (approx.) |
| External DC Input |
DC 12V adaptor (for safety purpose, the adaptor must be certified with 600Visolation protection) |
| LCD update rate |
1 times / sec |
| No. Of Samples/Period |
1024 |
| Operating Humidity |
< 85% relative |
| Operating Temperature |
-10°C to 50°C |
| Storage Humidity |
< 75% relative |
| Storage Temperature |
- 20°C to 60°C |
| Weight(6800) |
1160g |
| Weight(6801) |
200g |
| Weight(6802) |
600g |
| Dimension(6800) |
257 (L) x 155 (W) x 57 (H) mm ,10.1"(L) x 6.1" (W) x 2.3" (H) |
| Dimension(6801) |
210 (L) x 62 (W) x 36 (H) mm ,8.3 " (L) x 2.5" (W) x 1.4" (H) |
|
|
|
TES- 1370 NDIR CO 2 METER
|
 |
 |
- CO 2 : 0 ~ 6,000 ppm range, Diffusion sampling mode.
- Three LCD Display for CO 2 , %RH Humidity and Air Temperature.
- Maintenance free dual wavelength NDIR infrared CO 2 sensor (non-dispersive infrared).
- Continuous or manual data logging (20,000 sets).
- Data hold & Maximum / Minimum with Time stamp.
- Data Memory and READ function.
- Alarm and Time setting.
- RS-232 function / Software.
- Backlight display function.
- Simple and safe to use.
|
 |
|
| Measuring Range |
CO 2 : 0~ 6,000 ppm
Temperature : -20℃ ~ 60℃ (-4℉ ~ 140℉)
Humidity : 10%RH ~ 95%RH
|
| Resolution |
CO 2 :1ppm
0.1℃ / 0.1℉ / 0.1%RH
|
| Accuracy |
CO 2 : ±3% of reading or ±50ppm, which is greater.
Temperature : ±0.5℃, ±0.9℉
Humidity : ±3%RH ( at 25℃, 30 ~ 95% RH ).
±5%RH ( at 25℃, 10 ~ 30% RH )
|
| Manual Data Memory Capacity |
99 sets (Direct reading from LCD display) |
| Auto Memory Capacity |
Approx. 20,000 sets |
| Operating Conditions |
5℃ ~ 50℃ (41℉ ~ 122℉)
10 ~ 90% R.H. |
| Power Source |
6pcs size AAA Alkaline Battery (large current) batteries. |
| Battery Life |
Approx. 8 hours by using alkaline (large current)
batteries (without backlight or Alarm function).
For long time datalogging, please use AC adapter. |
| Size |
158(L) ×72(W) ×35(H)mm |
| Weight |
Approx. 255g (including batteries) |
| Accessories |
Instruction Manual, Battery, AC Adaptor (110Vor220V),
Software CD Rom, RS232 Cable & Carrying case. |
|
|
|
|
|
|
TES-52 Sound Level Meter
|
 |
 |
- 0.1dB Resolution
- Range from 30 to 130dB
- A&C frequency weighting
- Fast/Slow Dynamic characteristic
- Maximum with Elapsed time
- Manual data memory and read
- 5Selectable Ranges
- Bargraph Indication
- Logging Function (99 Sets)
|
 |
|
| Applicable standards |
IEC Pub 60651 Type2 , ANSI S1.4 Type 2 |
| Digital display |
4 digital LCD,0.1 dB resolution ,updated every 0.5s |
| Measurement Level |
30dB to 130dB |
| Measurement Frequency range |
31.5 Hz to 8KHz |
| Frequency Weighting |
A and C |
| Time weight |
Fast and Slow |
| Microphone |
1/2 inch Electret condenser microphone |
| Measureement level range |
5 ranges in 10-dB step : 30~90dB , 40~100dB
50~110dB , 60~120dB
70~130dB
|
| Quasi-analog bar indicator |
1-dB steps, 60dB display range, updated every 0.125s |
Display Warning function
Overrange indicator
Underrange indicator |
Displayed at the upper limit
Displayed at the lower limit |
| Manual data memory capacity |
99 sets |
| Analong AC / DC output |
2Vrms ( at full scale ) , 10mVDC / dB |
| Power supply |
Four 1.5V LR-6/AA size alkaline cell, AC adapter |
| Battery Life |
about 50 hours |
| Operating temperature , humidity |
0 ℃ ~ 50 ℃ (32 ℉ ~122 ℉ )R.H.<80% non-condensing
-10 ℃ ~60 ℃ (14 ℉ ~140 ℉ )R.H<70% non-condensing
|
| Dimensions |
258 (L)×68(W)×27(H)mm |
| Weight |
Approx. 310g |
| Accessories |
Instruction manual , Battery ,
Adjustment screwdriver , Wind shield |
|
|
|
|
|
|
TES-1339 Light Meter Pro.
|
 |
 |
- Dual Display, 4-digit LCD reading.
- Spectral Sensitivity close to CIE photopic Curve.
- Measuring Levels Ranging 0.01 to 999900 Lux,0.01 to 99990 fc, Autoranging 5 step.
- Accurate and Instant response.
- Integral illuminance measurement.
- Luminous intensity measurement.
- Data Hold function.
- Data memory and read function.
- Reference value setting for relative or percentage deviation measurement.
- Ripple measurement for STRAY + LIGHT function.
- Time-hold function.
- Point - average function.
- Comparator function.
- Auto power off function.
- CNS 5119 Class Ⅱ .
|
 |
|
| Display |
Dual display 4 digit LCD read out. |
| Measuring Range |
99.99, 999.9, 9999, 99990, 999900 Lux
9.999, 99.99, 999.9, 9999, 99990 fc
Auto rangeing (5 step) (1 fc = 10.76 Lux) |
| Overrange Display |
OL is displayed |
| Resolution |
0.01 Lux, 0.001 fc |
| Accuracy |
± 3% rdg ± 5dgt (Calibrated to standard
incandescent lamp, 2856° Κ ) |
| CIE photopic f ' 1 |
≦ 6 % |
| Temperature Characteristics |
± 0.1%/ ℃
|
| Measuring Rate |
Approximately 5 time/sec |
| Photosensor |
Silicon photodiodes |
| Data Memory Capacity |
50 sets. (Direct reading from LCD display) |
| Operating / Storage Conditions |
0 ℃ ~ 50 ℃ <80% RH
-10 ℃ ~ 60 ℃ <70%RH |
| Power Source |
6 pcs AAA size Battery |
|
Battery Life (typical)
|
100 hours |
| Photosensor Lead Length |
150 cm (approx.) |
| Photosensor Dimensions |
100(L) × 60(W) × 27(H)mm |
| Dimension |
150(L) × 72(W) × 33(H)mm |
| Weight |
250g |
| Accessories |
Carrying case, Instruction manual, Battery |
|
|
|
|
|
|
TES-1326S/1327/1237K Infrared Thermometer
|
 |

|
- 0.1 ℃/0.2 ℉ Resolution
- -20 ℃ ~ 500℃
- Built-in Laser Sighting/Backlight LCD display
- Memory / Read logging Capacity (50 Sets) (1327)
- Adjustable emissivity (1327)
- Audible and visible alarm (1327/1237K)
- MAX / MIN Reading
- Data memory and read function (1327/1237K)
- Emissivity adjustable (1327/1237K)
|
 |
|
| Display |
Backlight LCD display |
| Measurement Range |
-35 ℃ ~ 500℃ (-4 ℉ ~ 932 ℉ ) |
| Resolution |
0.1 ℃ / 0.2 ℉ |
| Accuracy |
± 2% reading or ± 2 ℃ |
| Spectral Response |
6 ~ 14μm |
| Field of View |
10 :1 optics ratio with a 1” min target |
| Emissivity |
0.17~1.00(1326:fixed 0.95) |
| Sighting |
Laser marker < 1mw |
|
| K-TYPE THERMOMETER(for 1327K): |
| Measurement Range |
-150 ℃~1350℃(-238 ℉~1999℉) |
| Resolution |
0.1 ℃ / 1℃ , 0.1℉ / 1℉ |
|
Function
|
Resloution
|
Range
|
Accuracy
|
|
℃
|
0.1 ℃
|
-150 ℃~0℃
|
±(0.2%rdg+1.0 ℃)
|
|
0 ℃~200℃
|
±(0.1%rdg+1.0 ℃ )
|
|
1 ℃
|
200 ℃~1350℃
|
±(0.2%rdg+2 ℃)
|
|
℉
|
0.1 ℉
|
-238 ℉~32℉
|
±(0.2%rdg+2 ℉)
|
|
32 ℉~200℉
|
±(0.1%rdg+2 ℉)
|
|
1 ℉
|
200 ℉~1999℉
|
±(0.2%rdg+4 ℉)
|
|
| Data memory capacity |
50 sets (Direct reading from LCD display)(1327/1327K) |
| Auto power off |
approx. 15 sec |
| Battery Life |
Approx. 100 hours (laser pointer and backlight aren't on use) (Alkaline) |
| Power Source |
One 9V cell( ANSI/NEDA-1604A,IEC-6LR61) |
| Operating / Storage Conditioon |
0 ℃~50℃ (32 ℉~122℉)below 80%RH -10℃~60℃(14℉~140℉)below 7%RH |
| Dimensions |
172mm*118mm*46mm |
| Weight |
220g |
| Accessories |
Instruction manual ,Battery |
|
|
|
|
|
|
TES-3600 3P4W POWER ANALYZER
|
 |
 |
- 10 Display Easy - to - View LCD Screen.
- Connectors for 4 Current Sensing Clamps.
- 1P2W, 1P3W, 3P3W2M & 3P4W Power Measurement.
- True RMS Sensing.
- Power KW, KVAR, KVA, PF, θ ,Hz, & Energy KWh, KVARh & KVAh Measurement.
- Phase sequency indicator function.
- Backlight display function.
- Manual Data Memory and Read (99 sets).
- Data Logging (512KB Memory, 20,000 sets)
- Programmable Trigger - Points and Start / Stop Time.
- RS-232 Optical Interface with three phase voltage / current Waveform display and Harmonic analysis.
- Easy - to - use Push - Button Operation.
- Light Weight, Portable Design.
|
 |
|
|
Ranges
|
Method
|
Accuracy
|
Input impedance
|
|
600.0V
|
True RMS
|
± 0.5%rdg ± 10dgts (>30V)
|
2M Ω
|
|
|
Ranges
|
Method
|
Accuracy
|
|
250A 、 500A 、 1000A
|
True RMS
|
± 0.5%rdg ± 10dgts+clamp on sensor specifications
|
|
| Active Power Measurement (KW) |
|
Ranges
|
Accuracy
|
Effect of power factor
|
|
600.0KW
|
± 0.5%rdg ± 10dgts+clamp on sensor specifications
|
± 0.1%rdg
|
|
| Reactive Power Measurement (KVAR) |
|
Ranges
|
Accuracy
|
Effect of power factor
|
|
600.0KVAR
|
± 0.5%rdg ± 10dgts+clamp on sensor specifications
|
± 0.1%rdg
|
|
| Apparent Power Measurement (KVA) |
|
Ranges
|
Accuracy
|
|
600.0KVA
|
± 0.5%rdg ± 10dgts+clamp on sensor specifications
|
|
| Power Integration Measurement |
|
Power Integration
|
Resolution
|
Accuracy
|
| | | | | | | | | | | |